SMA Solar Technology AG
Parameter
Description
Ratio of current trans-
Transformation ratio for cur-
ducer
rent measurement
Assign measurement
Overview of the activated
points
devices, e.g. PV inverters
Requirement:
☐ You must be logged in as Installer.
☐ You must have performed all necessary settings in the area Internal measurement devices in the menu
Measurement devices general configurations (see Section 7.5.1, page 55).
Procedure:
1. Set the desired parameters in the menu Measurement devices general configurations (see
SMA Fuel Save Controller user manual).
2. To activate or deactivate devices for the selected measurement device, select the button [Show devices] in the
Assign measurement points bar (see Section 7.5.4, page 61).
3. To continue with system settings, select the [Continue wizard] button.
4. Select the [Done] button.
5. End the system settings (see Section 7.9.1, page 67).
7.5.3
Making Detailed Settings on Measurement Devices for
Data Acquisition Modules
The parameters can only be set on this page if a Data Acquisition Module has been installed.
The system settings of the Fuel Save Controller can only be adjusted when the Fuel Save Controller is in STANDBY or
ERROR mode. The operating state STANDBY can be reached by stopping the SMA Fuel Save Controller.
Measurement devices detailed configuration
Figure 23: Detailed system settings for measurement devices that are connected via a Data Acquisition Module (example)
User Manual
Value
Explanation
The requirements of the measurement inputs must be complied
with (see installation manual of the Fuel Save Controller).
Devices can be activated or deactivated for the selected mea-
surement device via the button [Show devices].
7 System Settings
Default value
FSC20-BA-xx-20
59