7 System Settings
Destruction of gensets due to insufficient reserve power
Once the SMA Fuel Save Controller and PV power plant have stopped, the PV power plant is no longer available as
energy supplier. Now only the gensets supply the loads. If the current reserve power of the gensets is insufficient for
supplying the power required by the loads, the gensets become overloaded Sustained overload of the gensets can
result in failure of the power supply and destruction of the gensets.
• Prior to stopping the Fuel Save Controller, always check whether the current reserve power of the gensets is
sufficient to cover the requirement of the loads.
– If the current reserve power of the gensets is insufficient, switch off the loads or connect additional gensets.
This increases the reserve power of the gensets.
• If the power management and the communication interface of the genset is not compatible with the
Fuel Save Controller, power management must be deactivated on the Fuel Save Controller. In this case, the
gensets must be monitored to ensure that sufficient reserve power is retained.
• Make sure that the setpoints for power management on the Fuel Save Controller and the gensets are set to the
same value.
Procedure:
1. Choose the menu Configuration Wizard via the page and menu selection.
2. In the Genset System bar, select the [Adjust] button.
3. Set the parameters in the menu Genset general configuration (see Section 4.8.3, page 20).
4. Select the [Continue wizard] button.
5. Set the parameters in the menu Generator configuration Wizard: detailed configuration (see Section 4.8.3,
page 20).
6. To change a particular parameter for all gensets, activate the Apply changes to all devices checkbox.
7. To change a particular parameter for individual gensets, deactivate the Apply changes to all devices
checkbox.
8. To continue with system settings, select the [Continue wizard] button.
9. Select the [Done] button.
10. End the system settings (see Section 7.9.1, page 67).
7.3

Configuring the PV Power Plant

The system settings of the Fuel Save Controller can only be adjusted when the Fuel Save Controller is in STANDBY or
ERROR mode. The operating state STANDBY can be reached by stopping the SMA Fuel Save Controller.
The system settings for the inverters are located in the menus PV general configuration and PV system
configuration wizard.