7 System Settings
Parameter
Description
Alias
Name for identification of
measurement devices
Enable this device
Determines whether the
Fuel Save Controller should
take the measurement de-
vice into account in the con-
trol of the PV diesel hybrid
system
Feeder number
Current measurement num-
ber (see
SMA Fuel Save Controller
installation manual)
Data source priority
Use of the measured values
from the Fuel Save Con-
troller in the event of a com-
munication connection fail-
ure
Grid type
Type of grid used for cur-
rent and voltage measure-
ment
Ratio of potential
Transformation ratio for
transducer
voltage measurement
58
FSC20-BA-xx-20
Value
Explanation
Yes
The Fuel Save Controller
takes the measurement de-
vice into account.
No
The Fuel Save Controller
does not take the measure-
ment device into account.
1 to 6
Single source
Connection to the device
carrying out the measure-
ments is disabled. Only the
measured values from the
Fuel Save Controller are
used.
Second source
Connection to the device
carrying out the measure-
ments is enabled. The val-
ues communicated by the
device have priority. If com-
munication fails, the mea-
sured values from the
Fuel Save Controller are
used.
Measurement
Connection to the device
priority
carrying out the measure-
ments is enabled. The val-
ues measured by the
Fuel Save Controller have
priority. In case of measure-
ment failure, the values
communicated by the de-
vice are used.
3PH-3L
Three-conductor utility grid
with three line conductors
3PH-4L
Four-conductor utility grid
with three line conductors
and one neutral conductor
The requirements of the measurement inputs must be complied
with (see installation manual of the Fuel Save Controller).
SMA Solar Technology AG
Default value
No
User Manual