8 System Control
Parameter
Description
GenPwrAtRtFilterTime Time constant for the active
power of the genset system
LoadPwrAtRtFilterTm
Time constant for the active
power of the loads
Requirement:
☐ You must be logged in as Installer.
Procedure:
1. Go to Control Functions > PV control functions > Reactive power control via the page and menu selection.
2. Set the desired parameters (see Section 4.8.3, page 20).
8.2.2
Setting the Control of the PV Power Plant Reactive Power According to
Electrical Load
Parameter overview
Figure 36: Reactive Power Management: Settings regarding the reactive power of the PV power plant
Parameter
Description
Enable
Enables this function
80
FSC20-BA-xx-20
Value
Explanation
0 s to 3600 s
0 s to 3600 s
Value
Explanation
Yes
Activates the function*
No
Deactivates the function
SMA Solar Technology AG
Default
value
1 s
1 s
Default
value
Yes
User Manual