6.2

Electrical connections

A switch or an omnipolar cut-off switch with a contact opening of at least 3 mm must be installed
on the mains power line; put the cut-off switch in OFF position and disconnect any buffer batteries
before performing any cleaning or maintenance operations.
Ensure that an adequate residual current circuit breaker with a 0.03 A threshold and a suitable
overcurrent cut-out are installed upstream the electrical installation in accordance with best
practices and in compliance with applicable legislation.
For power supply, use a H07RN-F 3G1.5 type electric cable and connect it to the terminals L
(brown), N (blue),
(yellow/green), located inside the control panel box.
Strip the insulation from the ends of the power cable wires which will be connected to the terminal
(see ref. D, fig. 3-4), and secure the cable with the cable retainer.
Measure the voltage on the primary mains power connection with a tester.
TRANSFORMER
For the Brushless automation system to function correctly, the mains power
voltage must be:
- 230Vac ±10% for the CTRL/P control unit.
220÷230
- 115Vac ±10% for the CTRL/P/115 control unit
A
V
N
L
V
A
If the detected value does not comply with the above specified values or is not
+
-COM
stable, the automation system may NOT operate efficiently.
Connections to the electrical distribution network and to any other low-voltage conductors in
the external section to the electrical panel must be on an independent path and separate from
the connections to the command and safety devices (SELV = Safety Extra Low Voltage).
Make sure that the mains power conductors and the accessory wires (24 V) are separated.
The cables must be double insulated, strip them near the relevant connection terminals and lock
them with clamps [B] (not supplied).
N
L
3
4
5 6
X-Y-Z
Y
7
8
9
M
X
Z
BATTERY (+)
BATTERY (-)
DESCRIPTION
Connection to mains power, 230 V AC ±10%. Fuse 5x20 T2A.
Secondary transformer input for 26 V AC motor power (SEC1) and for 19 V power to logi-
cal control and peripheral devices (SEC2).
N.B.: Ready wired in factory by ROGER TECHNOLOGY.
Connection to ROGER brushless motor.
N.B.: Ready wired in factory by ROGER TECHNOLOGY.
Warning! If the motor wires become disconnected from the terminal board, after recon-
necting correctly, the travel must be acquired again as described in chapter 11.
Connection to AG/BAT/KIT or BI/BAT/KIT battery kit (see fig. 18-19)
See instructions for B71/BCHP or BI/BCHP for further information.
57