Commands And Accessories - Roger Technology CTRL/P Instrucciones Y Advertencias Para El Instalador

Centrale di comando per barriere elettromeccaniche versione per parcheggi
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 141
7

Commands and Accessories

If not installed, safety devices with NC contacts must be jumpered at the COM terminals, or disabled by modifying the
parameters
,
and
KEY:
N.A. (Normally Open) .
N.C. (Normally Closed).
CONTACT
11(+SC)
10(COM) Barrier open/closed indicator lamp, 24 Vdc 3 W.
11(+SC)
13(COM) Photocell test function and/r battery saving mode connection.
11(+SC)
13(COM) Indicator lamp connection for signalling the ACS/BA/60 detachable boom system sensor
12(+LUCI)
13(COM) Input for connecting AG/ALED-ALED series signal lights on boom (optional). 24 Vdc 6 W
14(+24V)
13(COM) Power feed for external devices, max. 10W. See technical specifications.
15(+ES)
17(COM) Input for connecting electric block.
16(+LAM)
17(COM) Connection for flashing light (24 V DC - max. 5 W).
21(ST)
22(COM) STOP command input (NC).
23(COS)
22(COM) Input (NC or 8.2 kOhm) for connecting sensing edge COS.
24(FT)
13(COM)
58
.
DESCRIPTION
The function of the indicator lamp is determined by parameter
The power feed for the photocell transmitters (TX) may be connected to terminal 11(SC).
Set the parameter
to enable the test function.
Each time a command is received, the controller unit switches the photocells off and on to
check that the contact changes state correctly.
Power feeds for all external devices (excluding the external radio receiver) may be connected
to reduce battery consumption (if batteries are used). Set
WARNING! If contact 11(SC) is used for the photocell test function or battery saving func-
tion, a barrier open indicator lamp cannot be connected.
anomaly or for signalling battery supply anomaly (battery exhausted. (Fig. 9)
The voltage level of the battery can be set via parameter
By connecting a RELAY to the SC output, an error alert signal contact can be achieved at an
external control system (fig. 9).
max.
10W 12V
(impulse activation, 1.5 seconds)
5W 12V
(normally powered electric lock)
The settings for the pre-manoeuvre flashing warning signal may be selected with parameter
, while the flashing mode is set with parameter
The opening of the safety contact causes the current operation to stop.
N.B.: the controller is supplied with this contact already jumpered by ROGER TECHNOLOGY.
Movement is reversed (open) if the sensing edge is activated during closure.
If the sensing edge is not installed, jumper the terminals 23(COS)-22(COM) or set
parameter
.
Input (NC) for connecting photocell FT (fig. 4-5-6).
The photocells are configured by default with the following settings:
. Photocell triggers only during barrier closure. Photocell is ignored during barrier
opening manoeuvre.
. Movement is reversed if the photocell is triggered during barrier closure.
. The barrier opens when an open command is received if the photocell FT is
obstructed.
If the photocells are not installed, jumper the terminals 24(FT) - 13(COM) or set the
parameters
and
WARNING! Use G90/F4ES or T90/F4S photocells.
In the case of installations with parking mode, the input FT is used to receive a closing
command from a magnetic loop (NC) (see chapter 14).
.
.
.
or
.
.

Publicidad

Tabla de contenido
loading

Tabla de contenido