1 English
Environment
IP20/UL Open Type: -10 °C to +50 °C (14 °F to 122 °F)
IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
Ambient
• When you install the drive in an enclosure, use a cooling fan or air conditioner to keep the
Temperature
internal air temperature in the permitted range.
• Do not let the drive freeze.
95% RH or less
Humidity
Do not let condensation form on the drive.
Storage
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Temperature
Pollution degree 2 or less
Install the drive in an area without:
• Oil mist, corrosive or flammable gas, or dust
• Metal powder, oil, water, or other unwanted materials
Surrounding Area
• Radioactive materials or flammable materials, including wood
• Harmful gas or fluids
• Salt
• Direct sunlight
1000 m (3281 ft) Maximum
Note:
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes
between 1000 m to 4000 m (3281 ft to 13123 ft).
It is not necessary to derate the rated voltage in these conditions:
Altitude
• Installing the drive at 2000 m (6562 ft) or lower
• Installing the drive between 2000 m to 4000 m (6562 ft to 13123 ft) and grounding the
• 10 Hz to 20 Hz: 1 G (9.8 m/s
Vibration
• 20 Hz to 55 Hz: 0.6 G (5.9 m/s
Installation
Install the drive vertically for sufficient airflow to cool the drive.
Orientation
■
Removing/Reattaching Covers
DANGER
energized drive. Before servicing, disconnect all power to the equipment and wait for the time specified on
the warning label at a minimum. The internal capacitor stays charged after the drive is de-energized. The
charge indicator LED extinguishes when the DC bus voltage decreases below 50 Vdc. When all indicators
are OFF, measure for dangerous voltages to make sure that the drive is safe. If you do work on the drive
when it is energized, it will cause serious injury or death from electrical shock.
22
neutral point on the power supply.
Contact Yaskawa or your nearest sales representative if you will not ground the neutral
point.
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an
YASKAWA TOMPC7106173UA GA500 Installation and Operation Instruction
Conditions
2
2
, 32.15 ft/s
)
2
, 19.36 ft/s
2
)