This section gives precautions to support the Safe Disable input. Contact Yaskawa for
more information.
The safety function complies with the standards shown in
Table 1.11 Applied Safety Standards and Unified Standards
Safety
Standards
IEC/EN 61508:2010 (SIL3)
IEC 62061:2005/AMD2:2015 (SILCL3)
Functional
EN 62061:2005/A2:2015 (SILCL3)
Safety
IEC 61800-5-2:2016 (SIL3)
EN 61800-5-2:2017 (SIL3)
Machine
ISO/EN ISO 13849-1:2015 (Cat.3, PL e)
Safety
IEC 61000-6-7:2014
EMC
EN 61000-6-7:2015
IEC/EN 61326-3-1:2017
IEC 61800-5-1:2007/AMD1:2016
LVD
EN 61800-5-1:2007/A1:2017
Note:
SIL = Safety Integrity Level.
Safe Disable Specifications
The Safe Disable input provides the stop function that complies with "Safe Torque Off" as
specified by IEC/EN61800-5-2. The Safe Disable input meets the requirements of ISO/
EN ISO 13849-1 and IEC/EN 61508. It also has a safety status monitor to detect safety
circuit errors.
When you install the drive as a component in a system, you must make sure that the
system complies with the applicable safety standards.
Refer to
Table 1.12
YASKAWA TOMPC7106173UA GA500 Installation and Operation Instruction
for safety function specifications.
Table
Unified Standards