Area of Use
Install this product in a location with Overvoltage Category III and pollution degree 2 or
less as specified in IEC/CE 60664.
■
Connect a Fuse to the Input Side (Primary Side)
The drive circuit protection must comply with EN 61800-5-1:2007 for protection against a
short circuit in the internal circuitry. Connect semiconductor fuses on the input side for
branch circuit protection.
Refer to
Single-Phase 200 V Class on page
and
Three-Phase 400 V Class on page 366
fuses.
WARNING
immediately energize the drive or operate peripheral devices. Wait for the time specified on the warning
label at a minimum and make sure that all indicators are OFF. Then check the wiring and peripheral device
ratings to find the cause of the problem. If you do not know the cause of the problem, contact Yaskawa
before you energize the drive or peripheral devices. If you do not fix the problem before you operate the
drive or peripheral devices, it can cause serious injury or death.
■
EMC Directive
Use drives with built-in EMC filters or install external EMC filters to the drive input side
to comply with the EMC Directive.
Drives with built-in EMC filters (models BxxxE, 2xxxE, 4xxxE) were tested in
accordance with European standard EN 61800-3:2004/A1:2012, and comply with the
EMC Directive.
■
Wire Selection
Select the correct wires for main circuit wiring.
Refer to
Main Circuit Wire Gauges and Tightening Torques (for CE Standards) on page
370
for wire gauges and tightening torques as specified by European standards.
Refer to
Main Circuit Wire Gauges and Tightening Torques (for UL Standards) on page
383
for wire gauges and tightening torques as specified by UL standards.
YASKAWA TOMPC7106173UA GA500 Installation and Operation Instruction
Electrical Shock Hazard. After the drive blows a fuse or trips an RCM/RCD, do not
Table 1.8 Icons to Identify Screw Shapes
Icon
365,
Three-Phase 200 V Class on page
for more information about recommended
Screw Shape
+/-
Slotted (-)
Hex socket cap (WAF: 5 mm)
1 English
366,