TEST mode

The TEST mode is used to test activation of the commands and safety devices with visual confirmation.
To activate the mode, press the TEST button with the automatic gate system at rest. If the gate is moving, pressing TEST stops
the gate. Pressing the button again enables TEST mode.
If the flashing light and the gate open indicator lamp illuminate for one second each time a control is used or a safety device
is activated.
Example: STOP contact in alarm state.
No safety device in alarm state, and no limit switch activated
STOP contact (N.C.) open. Jumper the STOP contact.
Sensing edge COS1 contact isn't connect or is open
Sensing edge COS2 contact isn't connect or is open
Photocell FT1 contact isn't connect or is open
Photocell FT2 contact isn't connect or is open
More than 3 limit switches activated
Gate completely open / Gate open limit switch activated
Gate completely closed / Gate closed limit switch activated
Limit switch on gate leaf 1 error
Limit switch on gate leaf 2 error
MOTOR 1 open limit switch activated
MOTOR 1 closed limit switch activated
MOTOR 2 open limit switch activated
MOTOR 2 closed limit switch activated
NOTA: If one or more contacts are open, the gate will not open or close. This does not apply for the limit switch signal state,
however, which is shown on the display but does not prevent normal operation of the gate.
If more than one safety device is in alarm state, once the problem relative to the first device is resolved, the alarm for the next
device is displayed. Any further alarm states are also displayed with the same logic.
Press the TEST button again to exit test mode.
After 10 seconds with no user input, the display returns to command and safety device state display mode.
9.4

Standby mode

POWER
56
The command signal status is shown on the left hand side of the display for
5 seconds, ONLY when the respective command signal is active (AP, CH, PP,
PE, OR).
For example, if the gate open command is activated, the letters AP
appear on the display.
The status of the safety devices/inputs is shown on the right hand side of the
display. The number of the terminal relative to the safety device in alarm
state flashes.
When the gate is completely open or completely closed, when the limit
switches are connected to the control unit, the display shows
shown on the display to indicate that the gate has reached the gate open
limit switch
or gate closed limit switch
This mode is activated after 30 minutes with no user input. The POWER LED
flashes slowly.
, + , - to reactivate the control unit.
Press UP
, DOWN
NOTE: If a safety password (only if active) is unlocked, to adjust the
parameter settings, the password is automatically reactivated in Stand
By mode.