Installing The Weld-In Version - ABB Sensyflow FMT500-IG Instrucciónes De Puesta En Marcha

Ocultar thumbs Ver también para Sensyflow FMT500-IG:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 159
Mounting
4.5.3

Installing the weld-in version

The weld-in version of the hot tap fitting is available in two overall lengths:
-
For nominal diameters DN 100 ... DN 125 (4 ... 5") and
-
For nominal diameters DN 150 ... DN 300 (6 ... 12").
The flowmeter sensor length is h = 425 mm (16.73 inches) in both cases.
The installation depth depends on the pipe diameter and is calculated individually.
Warning
Do not shorten hot tap fitting components or interfere with the design.
This can lead to the measuring medium escaping in an uncontrolled manner.
This can result in severe injuries or death.
Fig. 12: Dimensions in mm (inches) Hot tap fitting in measuring position.
1 Flowmeter sensor
2 Centering pin
20 - EN
1
2
Ø50
(2)
G00852
Flow direction
Sensyflow FMT500-IG
Calculating the installation depth (hot tap
fitting in measuring position):
X = h - (Ø pipe exterior / 2)
Y = (Ø pipe exterior / 2) - 28
Example:
Transmitter with overall length h = 425 mm
Pipe with external diameter of 210 mm
Hot tap fitting is in measuring position
X = 425 mm - (210 mm / 2) = 320 mm
CI/FMT500-IG-X1

Publicidad

Tabla de contenido
loading

Tabla de contenido