In the case of a 24 V UC power supply, the device may only be supplied with a safely isolated
low voltage (DIN VDE 0106).
Under no circumstances, connect the line voltage (115 V AC or 230 V AC) to the 24 V UC
input. Doing so would damage the device electronics beyond repair.
The maximum rated current for the overcurrent protection device on the installation side is
16 A.
6.3

Switching on

Warning
Before switching the device on, check that all the tasks described in the previous sections
have been carried out correctly.
Failure to observe the information provided can result in severe injuries or death.
Check again to ensure that the set operating voltage matches the power supply voltage.
Warning
Switching the device on while the rear housing cover is open can result in an electric shock; in
potentially explosive atmospheres, there is an additional risk of explosion.
This can result in severe injuries or death.
Only switch on the power supply when the housing cover is closed.
Switching on the power supply
The system will boot automatically and the device will be initialized. The device will then switch
to the set display screen and enter measuring mode.
Important (Notice)
If an error is detected during the system boot phase or during measurement, the problem will
be automatically highlighted on the display ("E" for error). The error can be read out in the
SERVICE MENU / STATUS MENU.
Parameterization (password-protected)
Local parameterization via display using magnetic pen (see Section 8, "Operation") or
parameterization via DTM in FDT 1.2 frame applications (e.g., SMART VISION).
Once a period of two minutes has elapsed following successful configuration or since the last
entry was made, the device automatically switches to the default display screen and reverts to
the STANDARD operation mode.
CI/FMT500-IG-X1
Sensyflow FMT500-IG
Commissioning
EN - 35