Mettler Toledo IND570 Manual Del Usuario página 65

Ocultar thumbs Ver también para IND570:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 79
2.4.6.6.
DeviceNet PLC Option
The DeviceNet PLC option board (Figure 2-50) is installed in position 3 (Figure 2-34) on the main
board. The DeviceNet option board is connected to the network by a DeviceNet-specific twisted pair
cable.
2.4.6.7.
EtherNet/IP – Modbus TCP PLC Option
The EtherNet/IP – Modbus TCP PLC option (Figure 2-51) is installed in position 3 (Figure 2-34) on
the main board. The EtherNet/IP-Modbus TCP PLC option connects to the network via a standard
Ethernet patch cable. The module's address is set in software, and the DIP switches are not used
and must all be set to OFF.
30205319
|
04
|
08/2016
Figure 2-50: DeviceNet PLC Option Board and Wiring
Notes for DeviceNet option wiring:
Connection with 2 twisted-pair shielded cables, Belden 3082A or 2083A or equivalent.
Refer to ODVA DeviceNet documentation (http://www.odva.org) for other considerations.
Wire sizes: 14 AWG max./22 AWG min.
Figure 2-51: EtherNet/IP-Modbus TCP Option Board
METTLER TOLEDO IND570 Weighing Terminal Installation Manual
2-35

Publicidad

Tabla de contenido
loading

Tabla de contenido