8. PHOTOCELLS TEST TPh
By enabling this function, before each movement starting from steady automation, the control unit does a functional check of the
photocells. The check will not be done in case of fast movement after the intervention of a safety device. Follow paragraph 5 for the
connections of the photocells.
9. SAFETY EDGE TYPE EDM
The control unit can work with two different types of safety edges:
•
edm = 0 : mechanical edge with normally closed contact.
•
edm = 1 : resistive edge 8,2Kohm.
10. OPERATION MODE OF SAFETY EDGE iED
To allow the installation of the safety edges in both the directions of movements, it is possible to choose 2 different functionings:
•
ied = 0 : only in closing with total inversion of the movement.
•
ied = 1 : in both directions of movements, it stops and short inversion of the movement to free the obstacle.
11. DECELLERATION RAMP DUE THE SAFETY COAST INTERVENTION Ebt
Through this parameter it is possible to adjust the duration of the decelleration ramp in case of the safety edge intervention. With
ebt = 0 there is an immediate interruption of the movement due the intervention of the safety edge.
12. REVERSE TIME ON SAFETY EDGE INTERVENTION ert
Through this parameter it is possible to adjust the time of reversal of the movement of the gate due the intervention of the safety
edge. You can configure the value from a minimum of 0.1 seconds (1), short inversion stroke, to a maximum of 2 seconds (20),
prolonged inversion.
13. SAFETY EDGE TEST TED
By enabling this function the control unit does a functional check of the safety edge. This function is used if the edge connected to
the control unit has an electronic self test (e.g. radio edge R.CO.O). Connect the test contact of the edge to the power supply of the
trasmitter of the photocells (chapter 5) ad enable the self test with low voltage 0Vdc (for the compatibility follow the instruction of
the safety edge with the electronic self test).
14. PARTIAL OPENING LPo
Partial opening can be performed only starting from a closed position. The parameter sets the opening like a percentage of the
total stroke.
15. AUTO RECLOSING TIME FROM PARTIAL OPENING TPC
Active when the automation is in the partial opening, it automatically closes after tpC seconds. In this phase the display shows
-TC with the blinking dash, that during the last 10 seconds will be replaced by the count down.
16. FLASHING LIGHT OUTPUT MODE FPr
It is possible to choose 2 different functionings for the blinker output:
•
fpr = 0 : fixed output. It will be necessary to connect a self flashing blinker (B.RO LIGHT 24 Vac).
•
fpr = 1 : flashing output. It will be necessary to connect a fix light blinker (B.RO LIGHT FIX 24 Vac).
17. PRE-FLASHING TIME TPr
Pre-flashing before each movement in both directions, tpr seconds of pre-flashing..
18. COURTESY LIGHT SETTINGS FCY
The control unit has 4 different functionings for the courtesy light:
•
fCy = 0 : the light switches off at the end of a movement after tCy seconds.
•
fCy = 1 : the light switches off only with closed automation after tCy seconds.
•
fCy = 2 : lighted on for tCy seconds from the beginning of a movement, indipendently on the conditions of the automa-
tion (the light could switch off before the end of the movement).
•
fCy = 3 : open automation light. The light switches off immediately when the automation reaches the closed position.
•
fCy = 4 : open automation light with proportional blinking:
– Opening: slow blinking.
– Closing: fast blinking.