code
range of
def.
display
variation
P0
20, ...,100
70
100
P1
2.0, ..., 19.9
5.0
P2
(1)
(P3), ..., 100
100
(P3),...60
60
P3
(1)
0, ..., (P2)
0
P4
0*, ..., 100
1
P5
2, ..., 100
10
P6
2.0, ..., 19.9
5.0
P7
(1)
(St), ..., 100
100
P8
2.0, ..., 19.9
5.0
P9
0, ..., 100
100
code
range of
def.
display
variation
d1
(2)
0.0, ...,199
read
d2
0.0, ..., 199
only
d3
0.0, ..., 199
d4
0, ..., 19k9
d5
0, ..., 1k5
d6
0.0, ..., 199
d9
0.0, ..., 199
(1)
: when accessing parameter A0, parameters P2, P3, P7 and St are automatically reset to the corresponding default value.
(2)
: in proportional operation (A0=1), d1 expresses the % of the control signal (see A0 and A2 in Table. 7.3.1).
Para visualizar los parámetros de control y las medidas, proceda del
siguiente modo:
1. pulse el botón PRG durante 5 segundos, hasta que aparezca el
código P0, que representa el primer parámetro (ver Fig. 7.2.1);
2. pulse el botón
o el botón
por los parámetros Px y dx, incluído el punto de consigna;
3. pulse el botón SEL para visualizar el valor del parámetro seleccio-
nado; durante 1 segundo aparece la unidad de medida del paráme-
tro;
4. pulse los botones
y
para modificar el valor;
5. pulse el botón SEL para confirmar temporalmente el valor visualiza-
do: aparecerá de nuevo el código ID del parámetro seleccionado;
6. pulse el botón PRG para finalizar la fase de programación.
Nota: Las modificaciones sólo se confirman pulsando el botón
PRG. Para más detalles, consulte el párrafo 7.4.
Leyenda:
1. pulse P0 durante 5 segundos, hasta que
aparezca P0;
2. pulse de forma repetida, para desplazarse
hasta el parámetro deseado;
3. pulse SEL para visualizar el parámetro
deseado.
control parameters
unit of
meas.
%
rH, °C
humidification differential
rH
high humidity or high
°C
temperature alarm threshold
rH, °C
low humidity/temp. alarm threshold
min
alarm delay (0*= 30 s)
rH
dehumidification dead zone
rH
dehumidification differential
rH
outlet set point
rH
outlet differential in
rH
high outlet alarm threshold
list of measurements
unit of
meas.
rH, °C, %
meas. signal from exter. regulator
rH
measurement from probe 2
kg/h
h
µS/cm
A
kg/h
para desplazarse de modo cíclico
deshum.
alarma
description
maximum production for H controllers
maximum production for P controllers
accessible only in control mode (A0=2, 3 or 4)
accessible only with the dehumidification function enabled
(b1 odd number) in humidity control mode (A0 = 2 or 3)
accessible only with outlet limiting control (A0=3)
description
not accessible in ON/OFF mode (A0=0)
accessible only with outlet limiting control (A0=3)
steam production (instant value)
hour counter
supply water conductivity
current
rated steam production
To display the control parameters and the measurements, proceed as
follows:
1. press the PRG button for around 5 seconds until the code P0
appears, representing the first parameter (see Fig. 7.2.1);
2. press the
or
parameters, including the set point;
3. press the SEL button to display the value of the selected parameter;
the unit of measure of the parameter is displayed for 1 second;
4. press the buttons
5. press the SEL button to temporarily confirm the value displayed: the
ID code of the selected parameter will be displayed again;
6. press the PRG button to conclude the programming phase.
Note: the modifications are confirmed only by pressing the PRG
button. For further details, see paragraph 7.4.
1
x1000
PRG
reset
2
SEL
3
Fig. 7.2.1
44
button to scroll cyclically through the Px and dx
and
to modify the value;
Key:
1. press PRG for 5 seconds until P0 is
displayed;
2. press repeatedly to scroll to the desired
parameter;
3. press SEL to display the desired
parameter.
humiSteam - cod. +030221914 rel. 5.2 - 07.11.2005
Table. 7.2.1
Table. 7.2.2