Troubleshooting Table - Carel humiSteam Serie Manual Del Usuario

Tabla de contenido

Publicidad

problem
the humidifier does not turn on
the humidifier does not start
operation
the humidifier loads up water
without producing steam
the thermal-magnetic overload
switch is activated
the humidifier wets the duct
the humidifier wets the floor below
causes
1. no electrical power;
2. external switch of the humidifier in position
0 (open);
3. control connectors badly connected;
4. broken fuses;
5. transformer fault
1. remote ON/OFF contact open (relay/terminals
AB – AB or 7I – 8I);
2. the humidistat has not been connected correctly;
3. humidistat fault
4. control signal not compatible with the type set
5. value measured by the probe/s higher than the
corresponding set point
1. too high steam inlet counterpressures;
2. inlet filter to the clogged cylinder;
3. limestone in the supply tank;
4. drain solenoid valve malfunction
1. thermal-magnetic overload switch is under-rated
2. over-current at the electrodes
1. the distributor is not installed correctly (too near
the top of the duct or the condensate return is
blocked);
2. system over-sized;
3. humidifier active when the fan in the duct is off
1. the humidifier drain is blocked;
2. the supply water or overflow circuit has leaks;
3. the condensate drain pipe does not bring the
water back to the supply tank;
4. the steam outlet pipe is not properly fastened to
the cylinder

10.4 Troubleshooting table

solution
1. check the protection devices upstream from the
humidifier and the presence of power;
2. close the switch on the panel: position I;
3. check that the connectors are properly inserted in
the terminal block;
4. check the condition of fuses F1/F2/F3;
5. check that the voltage across the secondary
winding of the transformer is 24Vac
1. close ON/OFF contacts (relay/terminals AB – AB or
7I – 8I);
2. check the external connection;
3. replace the humidistat
4. set parameters A0, A2-A9 correctly
5. check the values of the set point St and P7
1. check that the steam inlet pipe is not folded or
choked;
2. clean the filter;
3. clean supply tank;
4. check the anomalous presence of 24Vac on drain
solenoid valve and/or drain solenoid replacement
1. check that the thermal-magnetic overload switch is
rated for a current of at least 1.5 times the rated
current of the humidifier
2. see description for alarm EH
1. check that the steam distributor is installed
correctly;
2. decrease the steam production set on the control;
3. check the connection of the device (flow switch
or differential pressure switch) slaving the humidifier
to the ventilation in the duct (terminals AB - AB or
7I – 8I)
1. clean the drain in the bottom tank;
2. check the entire water circuit;
3. check the correct position of the condensate
drain pipe in the supply tank;
4. check the fastening of the pipe clamps on the
steam outlet
69
humiSteam - cod. +030221914 rel. 5.2 - 07.11.2005
Table. 10.4.1