Wilo Flumen OPTI-TR 20-1 Instrucciones De Instalación Y Funcionamiento página 297

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 1092
6.5.1
Fuse on mains side
6.5.2
Maintenance tasks
6.5.2.1
Checking the insulation resistance
of the motor winding
6.5.2.2
Test the resistor of the temper-
ature sensor
Installation and operating instructions Wilo-Flumen OPTI-TR 20-1, 28-1, 30-1, 40-1 Wilo-Flumen EXCEL-TRE 20, 30, 40
Installation and electrical connection
DANGER
Risk of explosion due to incorrect connection!
• Always connect the mixer to an electrical outlet outside the explosive area. If
the connection must be made within the explosive area, then the connection
must be carried out in an Ex-rated housing (ignition protection class
DIN EN 60079‑0)! Non-compliance will lead to a risk of fatal injury from explo-
sion!
• Connect the equipotential bonding conductor to the earth terminal indicated.
The earth terminal is installed in the area of the connection cable. A cable cross-
section in accordance with the locally applicable regulations must be used for
the equipotential bonding conductor.
• The connection must always be carried out by a qualified electrician.
• For the electrical connection, also note the additional information in the chapter
on potentially explosive areas found in the appendix of these installation and
operating instructions!
▪ The mains connection must match the specifications on the rating plate.
▪ Power supply on mains side for three-phase current motors with clockwise rotating
field.
▪ Lay the connection cable in accordance with the locally applicable regulations and con-
nect it according to the wire assignment.
▪ Connect the monitoring devices and check their function.
▪ Earth the device properly in accordance with applicable local regulations.
Circuit breaker
The size and switching characteristics of the circuit breakers must conform to the rated
current of the connected product. Observe local regulations.
Motor protection switch
Make provision for an on-site motor protection switch for devices without a plug! The
minimum requirement is a thermal relay/motor protection switch with temperature
compensation, differential triggering and anti-reactivation device in accordance with
the local regulations. In case of sensitive mains, make provision for the installation on-
site of other protective equipment (e.g. overvoltage, undervoltage or phase failure re-
lay, etc.).
Residual-current device (RCD)
Comply with the regulations of the local energy supply company! The use of a residual-
current device is recommended.
If persons come into contact with the device and conductive fluids, secure the connec-
tion with a residual-current device (RCD).
Carry out the following maintenance tasks prior to installation:
▪ Check the insulation resistance of the motor winding.
▪ Test the resistance of the temperature sensor.
▪ Test the resistance of the pencil electrode (optionally available).
If the measured values differ from the specifications:
▪ Moisture may have penetrated into the motor or the connection cable.
▪ The monitoring device may be defective.
Contact customer service in the event of a fault.
Use an insulation tester to measure the insulation resistance (measuring
voltage = 1000 V). Observe the following values:
▪ At the time of initial commissioning: Insulation resistance may not be less than 20 MΩ.
▪ For further measurements: Value must be greater than 2 MΩ.
Measure the resistor of the temperature sensors with an ohmmeter. The following
measured values must be complied with:
▪ Bimetallic strip: Measured value = 0 Ohm (passage).
en
297

Publicidad

Tabla de contenido
loading

Tabla de contenido