Before Switching On; Switch On And Off - Wilo Flumen OPTI-TR 20-1 Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 1092
en
7.5

Before switching on

7.6

Switch on and off

7.7
During operation
302
Commissioning
Approval accord-
ing to
CSA-Ex
Legend
− = not available/possible, o = optional, • = standard
For use in explosive atmospheres, the mixer must be marked as follows on the rating
plate:
▪ "Ex" symbol of the corresponding approval
▪ Ex classification
For the relevant requirements, refer to the explosion protection chapter in the ap-
pendix of these installation and operating instructions!
ATEX approval
The mixers are suitable for operation in potentially explosive atmospheres:
▪ Device group: II
▪ Category: 2, zone 1 and zone 2
Mixers must not be used in zone 0!
FM approval
The mixers are suitable for operation in potentially explosive atmospheres:
▪ Protection class: Explosionproof
▪ Category: Class I, Division 1
Notice: If the cabling is carried out according to Division 1, installation in Class I, Divi-
sion 2 is also permitted.
Before activating the mixer, check the following points:
▪ Check whether the device has been installed properly and in accordance with the locally
applicable regulations:
– Has the mixer been earthed?
– Has the connection cable route been checked?
– Has electrical connection been made in accordance with regulations?
– Are mechanical components attached correctly?
▪ Check the operating conditions:
– Min./max. fluid temperature checked?
– Max. immersion depth checked?
– Intermittent operation: Max. switching frequency complied with?
▪ Check installation location/operating space:
– Has the minimum water level above the propeller been defined and monitored?
– Min. fluid temperature can drop below 3 °C: Monitoring device with automatic deac-
tivation installed?
– No installations within the direct rotary range of the propeller?
The mixer must switch on and off using a separate operating point (on/off switch,
switchgear) set by the customer.
During the start process, the rated current is exceeded for several seconds. Current
consumption continues to be slightly above the rated current until the operating tem-
perature of the motor is reached and the flow in the basin increases. During regular op-
eration, the rated current should no longer be exceeded. CAUTION! If the mixer does
not start up, switch off immediately. Remove the fault before reactivating!
WARNING
Risk of burns from hot surfaces!
Motor housing can become hot during operation. It may cause burns. Allow the mo-
tor to cool down at ambient temperature after switching it off!
WILO SE 2019-01