The unit is designed for outdoor installation. The unit should be correctly
levelled and positioned on a supporting surface capable of sustaining its
full weight, it must not be installed on brackets or shelves.
EQPI3X 270÷2100
L1
mm
L2
mm
L3
mm
L4
mm
EQPI3X 2115-2130
L1
mm
L2
mm
L3
mm
L4
mm
N.B.
The space above the unit must be free of any obstacles. If the unit is com-
pletely surrounded by walls, the distances specified are still valid, provided
that at least two adjacent walls are not higher than the unit itself.
There must be a minimum gap of at least 3.5m between the top of the
unit and any obstacles above it.
If more than one unit is installed, the minimum distance between the
finned coils should be at least 2 m.
However it is installed, the coil inlet air temperature (ambient air) must
remain within the set limits.
II.6.4 Reduction of unit's noise level
Correct installation envisions taking measures aimed at reducing the noise
inconvenience from the unit's standard operation.
IMPORTANT!
Incorrect positioning or installation of the unit may amplify noise
levels and vibrations generated during operation.
• non-soundproofed reflecting walls near the unit, such as terrace walls or
building perimeter walls, may increase the total sound pressure level re-
ading near the appliance by as much as 3 dB(A) for every surface (e.g. a 6
dB(A) increase corresponds to 2 corner walls);
• install suitable anti-vibration mountings under the unit to avoid transmit-
ting vibrations to the building structure (SAG - anti-vibration mountings);
• make all water connections using elastic joints, pipes must be firmly sup-
ported by solid structures. If the pipes are routed through walls or panels,
insulate with elastic sleeves.
44
EQPI3X
1500
2000
1500
1000
2000
2000
2000
1500
• on top of buildings, solid floor frames can be provided which support the
unit and transmit its weight to the support elements of the building;
• If, after installation and start-up of the unit, structural vibrations are observed
in the building which provoke such strong resonance that noise is generated
in other parts of the building, consult a qualified acoustic technician for a
complete analysis of the problem.
II.7 Weight distribution
Dividing the weight
This section of the manual gives indications concerning weight distribution
on the unit. Knowing these values is of the utmost importance for dimen-
sioning the surface upon which the unit will be installed. The unit is intended
for installation both at ground floor and at the top of buildings. Correct
installation and positioning includes levelling the unit on a surface capable of
bearing its weight.
II.7.1 EQPI3X
Models 270÷2100
EQPI3X-EQPI3XS
Weight
270
280
290
(*)
kg
1095
1120
1130
Support
A
kg
254
275
265
B
273
276
281
kg
C
kg
295
285
301
D
274
284
284
kg
EQPI3X
with PUMP DP2, RC100 and DPR2 accessory
EQPI3X-EQPI3XS
Weight
270
280
290
(*)
kg
1325
1350
1360
Support
A
kg
254
259
261
B
387
396
395
kg
C
kg
413
421
423
D
271
275
280
kg
EQPI3X
with PUMP ASDP2 accessory
EQPI3X-EQPI3XS
Weight
270
280
290
(*)
1325
1350
1360
kg
(**)
1660
1685
1695
kg
Support
A
kg
260
265
284
B
612
653
617
kg
C
kg
554
546
544
D
235
221
251
kg
Weight of the unit when empty
*
**
Weight of the units including the water present in the tank
N.B.
The weight of the EQPI3X units also includes the INS accessory (standard in
EQPI3XS models).
Models 2115÷2130
EQPI3X-EQPI3XS
2100
Weight
2115 2130
(*)
1140
kg
1485
1505
Support
A
288
kg
363
363
B
271
348
357
kg
C
282
kg
379
389
D
299
395
396
kg
with PUMP DP2, RC100 and
DPR2 accessory
EQPI3X
2100
Weight
2115
2130
(*)
1370
kg
1760
1780
Support
A
264
kg
352
353
B
398
467
477
kg
C
426
kg
537
546
D
283
404
404
kg
with PUMP ASDP2, RC100 and
DPR2 accessory
EQPI3X-EQPI3XS
2100
Weight
2115
2130
(*)
1370
1760
1780
kg
1705
(**)
2335
2355
kg
Support
A
287
kg
432
431
B
619
763
772
kg
C
546
kg
728
739
D
253
412
413
kg