6
Commands and Accessories
modifying the parameters
N.A. (Normally Open) .
N.C. (Normally Closed).
CONTACT
8
9(COR)
10(+SC)
11(COM)
10(+SC)
11(COM)
12(FT2)
30(COM)
13(FT1)
30(COM)
14(COS2)
16(COM)
15(COS1)
16(COM)
17(ST)
16(COM)
22
21(ANT)
,
,
,
,
and
DESCRIPTION
Output (potential free contact) for connecting courtesy light. 230 Vac 100 W - 24 Vac/dc 40 W.
NOTE: Provide a protective fuse.
•
•
The COR output operating mode is managed by parameter
The voltage level of the battery can be set via parameter
Connection for gate open indicator lamp. 24 Vdc 3 W.
The function of the indicator lamp is determined by parameter
Photocell test connection and/or battery saving.
The power feed for the photocell transmitters (TX) may be connected to 10(+SC).
Set the parameter
to enable the test function.
that the contact changes state correctly.
Power feeds for all external devices may be connected to reduce battery consumption (if bat-
teries are used). Set
or
WARNING! If contact 10(+SC) is used for the photocell test function or battery saving function,
a gate open indicator lamp cannot be connected.
Input (NC) for connecting photocells FT2
The photocells FT2
–
. Photocell FT2 disabled when gate is opening.
–
. Photocell FT2 disabled when gate is closing.
–
. The gate opens when an open command is received if photocell FT2 is obstructed.
If the photocells are not installed, jumper the terminals 30(COM) - 12(FT2) or set the
parameters
and
.
WARNING! Use F4ES or F4S series photocells.
Input (NC) for connecting photocells FT1
The photocells FT1
–
. Photocell triggers only during gate closure. Photocell is ignored during gate opening.
–
.
–
. The gate opens when an open command is received if photocell FT1 is obstructed.
If the photocells are not installed, jumper the terminals 30(COM) - 13(FT1) or set the
parameters
and
.
WARNING! Use F4ES or F4S series photocells.
–
. The sensing edge COS2 (NC contact) is disabled.
If the sensing edge is not installed, jumper the terminals 14(COS2) - 16(COM) or set the pa-
rameter
.
–
. The sensing edge COS1 (NC contact) is disabled.
If the sensing edge is not installed, jumper the terminals 15(COS1) - 16(COM) or set the pa-
rameter
.
STOP command input (NC).
The current manoeuvre is arrested if the safety contact opens.
N.B.: the controller is supplied with this contact already jumpered by ROGER TECHNOLOGY.
Antenna connector for slot-in radio receiver board.
N.B.
.
.
.
.
COS2.
COS1.
.
.
57