The response of the obstacle detection system is a 70% reduction in maximum torque for a period of 1 s.
The response of the obstacle detection system is a 80% reduction in maximum torque for a period of 2 s.
The response of the obstacle detection system is a 100% reduction in maximum torque for a period of 3 s.
The response of the obstacle detection system is a 100% reduction in maximum torque for a period of 5 s.
Setting opening and closing speed
N.B.:
See chapter 13
01= 6 m/min ... 10= maximum speed.
Setting end of manoeuvre constant approach speed
Once deceleration is complete, the gate continues to the limit switch at constant speed. The distance is set with
the parameters
and
.
01= 2 m/min; 02= 2,5 m/min; 03= 3 m/min; 04= 3,5 m/min; 05= 4 m/min.
Setting number of automatic closure attempts after activation of sensing
edge or obstacle detection (crush protection)
No automatic closure attempts.
From 1 to 3 automatic closure attempts.
We recommend setting a value equal to or lower than the value set for parameter
Automatic closure is only performed if the gate is completely open.
Setting photocell mode during gate opening (FT1)
STOP. The gate stops and remains stationary until the next command is received.
photocell is cleared.
DELAYED REVERSE. The gate stops if the photocell is obstructed. The gate closes when the photocell is cleared.
Setting photocell mode during gate closing (FT1)
STOP. The gate stops and remains stationary until the next command is received.
photocell is cleared.
DELAYED REVERSE. The gate stops if the photocell is obstructed. The gate opens when the photocell is cleared.
Photocell (FT1) mode with gate closed
This parameter is not visible if
If the photocell is obstructed, the gate cannot open.
The gate opens when an open command is received, even if the photocell is obstructed.
The photocell sends the gate open command when obstructed.
Setting photocell mode during gate opening (FT2)
STOP. The gate stops and remains stationary until the next command is received.
photocell is cleared.
DELAYED REVERSE. The gate stops if the photocell is obstructed. The gate closes when the photocell is cleared.
Setting photocell mode during gate closing (FT2)
,
or
is set.
.
69