Descargar Imprimir esta página

SKF LINCOLN Centro-Matic P653S Serie Instrucciones De Uso Y Mantenimento página 22

Ocultar thumbs Ver también para LINCOLN Centro-Matic P653S Serie:

Publicidad

Idiomas disponibles

Idiomas disponibles

Factory settings for parameters
Programming steps
Factory setting
P1
00
NO
02
SP
35
09
Description
Pause time – 0 to 59 hours
Pause time – 0 to 59 minutes
Output of both fault relays
NO (normally open)
NC (normally closed)
Two options for signalling a fault
o1 (Option 1)
F1 relay contact
a) Low-level fault will cause F1 contact to repeatedly open and close.
b) Pressure fault will cause F1 contact to close and stay closed.
F2 relay contact
Low-level fault or pressure fault will cause F2 contact to close and stay closed.
o2 (Option 2)
F1 fault relay's contact will close on a low-level fault
F2 fault relay's contact will close on a pressure fault
Both contacts can be used for remote signalling.
Option to have pump start with pause time or lube cycle.
SP – Pump starts with a pause time
SO – Pump starts with a lube cycle
P7 programming step will only appear on pump with internal pressure transducer. (Reading x 100)
35 x 100 = 3 500 psi. 3 500 psi (241 bar) is maximum pressure that pump will build. Adjustable
from 1 400 to 4 600 psi (96 to 317 bar) in 100 psi (6,9 bar) increments.
P8 programming step will only appear on pump with external pressure transducer.
(Reading x 100) 09 x 100 = 900 psi. 900 psi (62 bar) is where = external pressure transducer will
open (vent) adjustable from 200 to 1 000 psi (13 to 69 bar) in 100 psi (6,9 bar) increments.
22

Publicidad

loading

Este manual también es adecuado para:

Lincoln centro-matic p653s-4-x-l-f-24-2a-as06