Parameter Mapping
The input and output assembly mappings of the inverter parameters are set in the parameters 3000 Input Mapping (PLC->inverter) and 3064
Output Mapping (inverter->PLC). Parameters created in the application may be added into the mapping. The mapping of each table ends on
the first zero entry.
The total number of input and output bytes mapped depends on the type of parameters
added to the mapping tables. The number of bytes used by each data type is summarized
in the table.
For the input mapping each parameter must be read-writable. Parameter
arrays are permitted. Configuration type parameters, string parameters,
password parameters and reserved parameters are not permitted. The
default input mapping is given in the table.
For the output mapping each parameter may be read-only or read-
writable. Parameter arrays are permitted. String parameters and
password parameters are not permitted. The default input mapping is
given in the table.
If the input and output mappings have invalid entries then the parameter 3130 EtherNet IP State will report ERROR and the inverter will not go
into the Operational state.
AC30 series Variable Speed Drive
AC30 Data Type
BOOL
SINT
INT
DINT
USINT (incl enumerated)
UINT
UDINT
REAL
TIME
DATE
TIME_OF_DAY
DATE_AND_TIME
BYTE
WORD
DWORD
Input Mapping Table
000
0627 Comms Control Word
001
0681 Comms Reference
002
0000
Output Mapping Table
000
0661 Status Word
001
0395 Actual Speed Percent
002
0000
A-13
Modbus TCP
Bytes
1
1
2
4
1
2
4
4
4
4
4
4
1
2
4
Data Type
Bytes
WORD
2
REAL
4
Data Type
Bytes
WORD
2
REAL
4