Dc Link Volts Limit - Parker AC30 Serie Manual Del Producto

Ocultar thumbs Ver también para AC30 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

D-48
Parameter Reference

DC Link Volts Limit

Parameters::Motor Control::DC Link Volts Limit
This function prevents over-voltage faults occurring due to a rapidly changing setpoint.
Parameter Name
No.
VDC Lim Enable
1641
Enable DC Link Volts Limit during a fast deceleration to prevent overvoltage trip
VDC Lim Level
1642
Determines the dc link volts at which the DC Link Volts Limit sequence is started.
Entered as a percentage of the max DC link voltage (drive overvoltage level = 100%).
VDC Lim Active
1643
Set True when the deceleration ramp is paused in order to limit the DC link voltage
VDC Lim Output
1644
This diagnostic represents the speed setpoint output of the DC Link Volts limit Feature in Electrical Hz
Path
Parameters::Motor Control::DC Link
Volts Limit
Parameters::Motor Control::DC Link
Volts Limit
Parameters::Motor Control::DC Link
Volts Limit
Parameters::Motor Control::DC Link
Volts Limit
Default
Range
FALSE
91.0
78.0 to 100.0
x.x
Min to Max
Units
Writable
STOPPED
STOPPED
%
NEVER
Hz