Parameter Name
No.
Drive Diagnostic
0688
Indicates the health of the drive configuration. When the drive configuration includes a mutually conflicting requirement, this parameter
indicates the problem; for example, it attempting to run in Closed Loop Vector control mode when no feedback option is configured.
Product Code Flags
1551
Manufacturing flags byte read from the power electronics stack.
Bit 0
When set, indicates that the dynamic brake switch power electronics is fitted. On larger frame sizes the brake switch is a
factory fit option. On frames C,D,E,F and G this bit is ignored.
Bit 1 – 7
Reserved
Manufacturing Flags
1636
Manufacturing flags word read from the control module.
Bit 0
When set, indicates that the drive is a special build.
Bits 1 – 15 Reserved
OEM ID
1256
A 16-bit integer set in the factory, that identifies the equipment manufacturer. This may be used to lock or tailor an application to a
given manufacturer. To obtain a unique ID apply to Parker Hannifin Electomechanical Drives Business Unit.
AC30 series Variable Speed Drive
Path
Parameters::Device Manager::Drive info
Parameters::Device Manager::Drive info
Parameters::Device Manager::Drive info
Parameters::Device Manager::Drive info
Parameter Reference
Default
Range
0:OK
1:STACK NOT CONNECTED
2:STACK DATA CORRUPT
3:UNKNOWN STACK
4:STACK MISMATCH
D-57
Units
Writable
NEVER
NEVER
NEVER
NEVER