D-100
Parameter Reference
Parameter Name
No.
Anin 01 Value
0039
Terminal X11.1
The value returned by the signal processing electronics. For unipolar ranges, (all except -10..10V), the value is expressed as a
percentage of the hardware range. For the -10..10V range the full range signal is expressed as -100% to +100%.
Anin 01 Break
0040
When the input range is set to 4..20mA a break is defined as an input signal less than 3mA. Otherwise this parameter is set to FALSE.
Anin 02 Value
0041
Terminal X11.2
The value returned by the signal processing electronics. For the 0..10V range the value is expressed as a percentage of the hardware
range, (0 to 100%). For the -10..10V range the full range signal is expressed as -100% to +100%.
Anout 01 Value
0042
Terminal X11.3
The desired output value expressed as a percentage of the output range.
Range
0..10V
0..20MA
4..20MA
Anout 02 Value
0043
Terminal X11.4
The desired output value expressed as a percentage of the output range.
Range
-10..10V
0..10V
Path
Same as PNO 38
Same as PNO 38
Same as PNO 38
Same as PNO 38
Mapping
0% gives 0V, 100% gives 10V
0% gives 0mA, 100% gives 20mA
0% gives 4mA, 100% gives 20mA
Same as PNO 38
Mapping
-100% gives -10V, 100% gives 10V
0% gives 0V, 100% gives 10V
Default
Range
x.x
-100.0 to 100.0
x.x
-100.0 to 100.0
0.00
Min to Max
0.00
Min to Max
Units
Writable
NEVER
%
NEVER
%
NEVER
%
ALWAYS
ALWAYS
%
AC30 series Variable Speed Drive