Idiomas disponibles

Parameter Name
No.
Alignment Ramp Time
1800
Time to install the amps into the motor phase with a linear ramp.
Alignment On Motor
1801
Selection of the motor phase when MANUAL method is selected. Can be
PHASE U : "Alignment Elec Pos" should be 90° -
PHASE V : "Alignment Elec Pos" should be 210° or -150°
PHASE W : "Alignment Elec Pos" should be 330° or -30°
Alignment Offset
1802
Represents the offset value needed to align Zero position to motor Back EMF
MANUAL : Value is calculated and passed back to 1808 PMAC Encoder Offset.
AUTOMATIC : Value that has been applied to align the 'encoder/resolver' to the motor phase U with controls on position and motor
phases.
If the Alignment is completed, then this parameter is written back to 1808 PMAC Encoder Offset
Alignment Elec Pos
1803
Actual electrical position
Alignment Direction
1804
AC30 series Variable Speed Drive
Path
Same as PNO 1796
Same as PNO 1796
Parameters::Motor Control::Pos
Fbk Alignment
Parameters::Motor Control::Pos
Fbk Alignment
Parameters::Motor Control::Pos
Fbk Alignment
Parameter Reference
Default
Range
1.000
0.000 to 30.000
0
0:PHASE U
1:PHASE V
2:PHASE W
x.x
-180.0 to 180.0
x.x
-180.0 to 180.0
0:STANDARD
1:REVERSE
D-135
Units
Writable
s
ALWAYS
ALWAYS
deg
NEVER
deg
NEVER