Parameter Name
No.
Spd Loop Aux Torq Dmd
0521
When the drive is operating in speed control mode, the value of this parameter is added on to the torque demand produced by the
speed loop PI. When the drive is operating in torque control mode (i.e. Set Torq Ctrl Only is TRUE) the speed loop PI does not
operate, and the torque demand becomes the sum of this parameter plus the DIRECT INPUT (if selected).
Spd Loop Adapt Thres
0523
If the speed demand is less than the Spd Loop Adapt Thres, the speed loop proportional gain is the Spd Loop Adapt Pgain.
Spd Loop Adapt Pgain
0524
Proportional gain used if speed demand < Spd Loop Adapt Thres.
Spd Demand Pos Lim
0525
This sets the upper limit of the speed demand.
Spd Demand Neg Lim
0526
This sets the lower limit of the speed demand.
Sel Torq Ctrl Only
0527
Selects between Speed Control mode and Torque Control mode. When TRUE, (Torque Control mode) the torque demand output from
the speed loop feature is the sum of the Direct Input plus the Spd Loop Aux Torq Dmd parameter.
AC30 series Variable Speed Drive
Path
Parameters::Motor Control::Spd Loop
Settings
Parameters::Motor Control::Spd Loop
Settings
Parameters::Motor Control::Spd Loop
Settings
Parameters::Motor Control::Spd Loop
Settings
Parameters::Motor Control::Spd Loop
Settings
Parameters::Motor Control::Spd Loop
Settings
Parameter Reference
Default
Range
0.00
-600.00 to 600.00
0.00
0.00 to 10.00
20.00
0.00 to 300.00
110.00
-110.00 to 110.00
-110.00
-110.00 to 110.00
FALSE
D-183
Units
Writable
ALWAYS
%
ALWAYS
%
ALWAYS
ALWAYS
%
%
ALWAYS
ALWAYS