Parker AC30 Serie Manual Del Producto página 385

Ocultar thumbs Ver también para AC30 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Parameter Name
No.
Anin 02 Offset
0959
The offset is expressed as a percentage of the hardware range selected by 0002 Anin 02 Type. For example, with the -10..10V range
an offset of 10% is equivalent to 1v on the input.
The offset is added to the measured value.
Anin 02 Scale
0960
The scale is a simple multiplication factor. The input voltage is converted to a percentage value. 0959 Anin 02 Offset is added and the
result is multiplied by 0960 Anin 02 Scale. The result is presented in parameter 0041 Anin 02 Value.
Anout 01 Type
0003
Analog output 1 is associated with terminal X11.3
The signal processing electronics for analog output 1 supports two output ranges:
0.
-10..10V
1.
0..10V
Anout 01 Scale
0686
The scale is a simple multiplication factor applied to 0042 Anout 01 Value.
1108
Anout 01 Offset
The offset is expressed as a percentage of the hardware range selected by 0003 Anout 01 Type. For example, with the -10..10V
range an offset of 10% is equivalent to 1v on the output.
The demand value 0042 Anout 01 Value is multiplied by 0686 Anout 01 Scale then added to the Offset. The resultant value is then
limited to -100 to 100%, (for the -10..10V type) or 0..100%, (for the 0..10V range).
AC30 series Variable Speed Drive
Path
Same as PNO 957
Same as PNO 957
Same as PNO 1
Setup::Inputs and Outputs::Base IO
Parameters::Inputs And Outputs::IO
Configure
Setup::Inputs and Outputs::Base IO
Parameters::Inputs And Outputs::IO
Configure
Parameter Reference
Default
Range
0.00
Min to Max
1.0000
Min to Max
0
Same as PNO 2
1.0000
Min to Max
0.00
Min to Max
D-93
Units
Writable
ALWAYS
%
ALWAYS
ALWAYS
ALWAYS
%
ALWAYS

Publicidad

Tabla de contenido
loading