D-154
Parameter Reference
Parameter Name
No.
Ramp Speed Output
0500
Output speed
Jog Setpoint
0501
The setpoint is the target reference that the Drive will ramp to
Jog Acceleration Time
0502
The time that the Drive will take to ramp the jog setpoint from 0.00% to 100.00%.
0503
Jog Deceleration Time
The time that the Drive will take to ramp the jog setpoint from 100.00% to 0.00%.
Stop Ramp Time
0504
Rate at which the demand is ramped to zero after the ramp has been quenched
Zero Speed Threshold
0505
Hold for zero speed detection used by stop sequences
Zero Speed Stop Delay
0506
Sets the time at which the Drive holds zero speed before quenching after a normal stop or a jog stop. This may be particularly useful if
a mechanical brake requires time to operate at zero speed, or for jogging a machine to position
Path
Parameters::Motor Control::Ramp
Parameters::Motor Control::Ramp
Parameters::Motor Control::Ramp
Parameters::Motor Control::Ramp
Same as PNO 484
Parameters::Motor Control::Ramp
Parameters::Motor Control::Ramp
Default
Range
x.x
-200.0 to 200.0
10.0
0.0 to 100.0
1.000
0.000 to 3000.000
1.000
0.000 to 3000.000
10.000
0.000 to 600.000
0.1
0.0 to 100.0
0.500
0.000 to 30.000