Parker AC30 Serie Manual Del Producto página 465

Ocultar thumbs Ver también para AC30 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Parameter Name
No.
Skip Frequency 4
1915
The centre frequency of skip band 4 in Hz.
Functional Description
Four programmable skip frequencies are available to avoid resonances within the mechanical system. Enter the value of frequency that causes the
resonance using a Frequency parameter and then program the width of the skip band using its Band parameter. The Drive will then avoid sustained
operation within the forbidden band as shown in the diagram. The skip frequencies are symmetrical and thus work in forward and reverse.
Setting a Frequency to 0 disables the corresponding band. Setting a Band to 0 causes the value of Band 1 to be used for this band.
Drive
Frequency
AC30 series Variable Speed Drive
Path
Setup::Application::Skip Frequencies
Frequency 1
Parameter Reference
Default
Range
0.0
0.0 to 1000.0
Frequency 2
D-173
Units
Writable
Hz
ALWAYS
Setpoint

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ac30pAc30d

Tabla de contenido