3.5 — Open Viewing Window
Rotate viewing window upward to access control panel.
1.
To hold viewing window in the open position, remove rod
2.
from clip at back of window and insert into hole in frame.
See Figure 3-5.
3.6 — Start and Run Engine
Pull up rubber flap covering fuse holder and verify installation of 7.5 amp fuse. See A of Figure 3-6.
1.
Move the Main Circuit Breaker switch down to the OFF (Open) position. See B of Figure 3-6.
2.
Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the
3.
MANUAL mode. See C of Figure 3-6.
Allow the engine to run until it reaches normal operating temperature.
4.
Press OFF on the control pad to stop the engine. A red LED illuminates to confirm that the system is in the OFF
5.
mode.
B
Main Circuit Breaker
Owner's Manual for Stationary Diesel Generators
LCD Screen
o
OFF
PUSH TO TRIP
Control Pad
Figure 3-6. Generator Control Panel
Figure 3-5. Viewing Window
7.5 Amp Fuse
and USB Port
C
Activation and Startup
A
13