IMPORTANT NOTE: Always use the applicable transfer switch owner's manual for actual manual transfer
switch operation instructions. The information presented here describes a typical V-style transfer switch,
which is not used for three phase applications.
4.10.1— Transfer to Generator Power
When utility power fails, manually transfer to standby power and start the generator as follows:
Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.
1.
Move the Main Circuit Breaker switch down to the OFF (Open) position.
2.
Turn off the utility power supply to the transfer switch using the means provided (such as a utility main line circuit
3.
breaker).
Use the manual transfer handle inside the transfer switch to move the main contacts to the STANDBY position
4.
(loads connected to the standby power source).
Press MANUAL on the control pad. The engine cranks and starts.
5.
Allow the engine to run for two minutes to bring it up to normal operating temperature.
6.
Move the Main Circuit Breaker switch up to the ON (Closed) position.
7.
Figure 4-4. Manual Transfer Switch Operation (Typical)
4.10.2— Transfer Back to Utility Power
When utility power is restored, manually transfer back to utility power and shut down the generator as follows:
NOTE: Verify that utility voltage has returned and is at the proper value.
Move the Main Circuit Breaker switch down to the OFF (Open) position.
1.
Allow the engine to run for two minutes at no-load to bring it up to normal operating temperature.
2.
Press OFF on the control pad to shut down the engine.
3.
Verify that utility power supply to the transfer switch is turned off.
4.
Use the manual transfer handle inside the transfer switch to move the main contacts to the UTILITY position
5.
(loads connected to the utility power source).
Turn on the utility power supply to the transfer switch using the means provided.
6.
Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.
7.
Owner's Manual for Stationary Diesel Generators
Manual Transfer
Handle
Transfer Switch
Operating Lever
NOTE: V-style transfer switch not used for three phase applications.
Load Connected to Utility
Load Connected to Standby
Operation
25