Procedural Veri Cations - Info Mode - Roger Technology B70/1DCHP Instrucciones Y Advertencias Para El Instalador

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 148
18

Procedural veri cations - INFO Mode

TEST
x5 s
INFO mode may be used to view certain parameters measured by the B70/1DCHP controller.
Press and hold the TEST button for 5 seconds from the "View command signals and safety devices" mode with
the motor stationary.
The control unit displays the following parameters and the corresponding measured values in sequence:
Parameter Function
.
View for 3 s the rmware version of the control unit.
Displays the position of MOTOR, expressed in revolutions and relative to total length, at the time of the test.
(example: .
View total length of programmed travel of MOTOR, in motor revolutions.
View motor speed of MOTOR, in revolutions per minute (rPM).
View current absorption of motor, in Amperes (e.g.: 001.1 = 1,1 A .... 016.5 = 16,5 A).
If the MOTOR is stationary, the current absorption value is 0. Activate a command function to test current ab-
sorption.
System OK indicator. To check for overloading (e.g.: too many utilities connected to 24 V output) or if the mains
voltage is too low, compare the parameters read with values indicated as follows with the motor stationary:
mains voltage = 230 V AC (nominal), bUS=
mains voltage = 207 V AC (-10%), bUS=
mains voltage = 253 V AC (+10%), bUS=
Display current, expressed in Amperes, used to compensate for strain detected by MOTOR due, for example, to
low external temperatures (e.g.: 0 = 0 A ... 4 = +12 A). At the beginning of a manoeuvre from the completely open
or completely closed position, if the control unit detects a strain higher than the value stored in its memory during
the travel acquisition cycle, the controller automatically increases the current delivered to MOTOR.
Display current threshold, expressed in Amperes, at which the obstacle detection function (crush prevention) of
MOTOR is triggered. This value is calculated automatically by the controller in relation to the settings of parame-
ters
and
For the motor to function correctly,
Indicates time taken by MOTOR to detect an obstacle, as set with parameter
E.g. .
= 1 s / .
If the control unit is capable of identifying the position of the gate when the test is conducted, the following is
shown on the display:
position known, normal operation.
position unknown, position recovery in progress.
Indicates the state of the automation system (open/closed).
automation system opening (motor active).
automation system closing (motor active).
automation system completely open (motor not actives).
automation system completely closed (motor not actives).
mains voltage too low or overload.
motors overcurrent.
Displays the number of thermal protection interventions of the inverter. If it displays a number different from 0000,
check that there are no excessive stress points and if the leaf, coming onto mechanical stops, does not activate
the limit switch.
Check the settings of parameters
Displays information about the electronic voltage limiter (ROGER TECHNOLOGY's TECHNICAL ASSISTANCE
ONLY).
• Use the + / - buttons to scroll through the parameters. When the last parameter in the sequence is reached,
press the - button to return through the previous parameters.
• In INFO mode, the automation system may be activated to test operation in real time.
• Press and hold the TEST button for a few seconds to exit INFO mode.
= motor installed on the left
.
.
.
must always be lower than the value
= 0.12 s (120 ms). Ensure that the manoeuvre time is more than 0.3 s.
and
.
...
;
= motor installed on the right
.
TEST
TO QUIT THE
INFO MODE
).
.
, in seconds.
1 click
81

Publicidad

Tabla de contenido
loading

Tabla de contenido