System Zero
█ █ █ █ █ █ █
Next
Cable length
Next
Exit
Important (Notice)
For additional information regarding operation of the LCD display, refer to chapter
"Operation".
For detailed descriptions of all menus and parameters, see chapter "Parameterization" of
the operating instruction.
CI/FEX300/FEX500-X1
Easy Setup
Ok
Easy Setup
5.0000 m
Edit
Menu
Easy Setup
Select
FEX300, FEX500
43. Use
to start automatic adjustment of system zero.
Important (Notice)
Prior to starting the zero adjustment, make sure that:
There is no flow through the flowmeter sensor
(close all valves, shut-off devices, etc.)
The flowmeter sensor is completely filled with the
fluid to be measured.
Enter the signal cable length between the transmitter and
the flowmeter sensor. For devices with a compact design
0.01 m must be entered.
44. Use
to call up the edit mode.
45. Use
or
to set the signal cable length.
46. Use
to confirm your selection.
Once all parameter have been set, the main menu appears
again. The most important parameters are now set.
47. Use
to switch to the process display:
Commissioning
EN - 49