Signal destinations for STW1_BM for telegram 220
Signal
Meaning
0 = OFF (OFF1)
STW1.0
= ON
0 = OFF2 (immediate pulse suppression and switching on inhibited)
STW1.1
1 = No OFF2 (enable possible)
0 = OFF3 (braking along the OFF3 ramp, then pulse suppression and switching on inhibited)
STW1.2
1 = No OFF3 (enable possible)
0 = Inhibit operation
STW1.3
1 = Enable operation
0 = Set ramp-function generator zero
STW1.4
1 = Enable ramp-function generator
0 = Freeze ramp-function generator
STW1.5
1 = Continue ramp-function generator
0 = Speed setpoint = 0
STW1.6
1 = Speed setpoint enable
STW1.7
= Acknowledge fault
STW1.8
Reserved
STW1.9
Reserved
STW1.10
1 = Control via PLC
STW1.11
Reserved
STW1.12
Reserved
STW1.13
Reserved
STW1.14
Reserved
STW1.15
Reserved
<1> STW1.10 must be set in order for the drive object to accept the process data (PZD).
<2> Interconnection is not inhibited.
1
2
DO: DC_CTRL
PROFIdrive - STW1_BM control word sector metal interconnection
<1>
<2>
<2>
<2>
<2>
3
4
Interconnection
Function diagram
Inverted
parameter
p0840[0] = r2090.0
[2580.1]
p0844[0] = r2090.1
[2580.1]
p0848[0] = r2090.2
[2580.1]
p2816[0] = r2090.3
[2655.7]
p1140[0] = r2090.4
[2580.3]
p1141[0] = r2090.5
[2580.3]
p1142[0] = r2090.6
[2580.3]
p2103[0] = r2090.7
[2546.1]
p0854[0] = r2090.10
[2580.3]
<2>
<2>
<2>
<2>
5
6
fp_2425_13_eng.vsd
26.10.18 V01.05.00
PROFIdrive sampling time
7
Function diagram
SINAMICS DCM
8
- 2425 -