Change fault response for a maximum of 20 faults <1>
p2100
[0]
0. Fault number
[1]
1. Fault number
[19]
19. Fault number
Change acknowledge mode for a maximum of 20 faults <1>
p2126
[0]
0. Fault number
[1]
1. Fault number
[19]
19. Fault number
<1> The fault response, acknowledge mode and message type for all faults and alarms are set to meaningful default values in the factory setting.
Changes that may be required are only possible in specific value ranges specified by SIEMENS.
When the message type is changed, the supplementary information is tranferred from fault value r0949 to alarm value r2124 and vice versa.
1
2
DO: All objects
Diagnostics - Faults/alarms configuration
p2101
[0]
Set fault response
0 = NONE
[1]
Set fault response
1 = OFF1
2 = OFF2
3 = OFF3
5 = Reserved
6 = Reserved
7 = Reserved
[19]
Set fault response
p2127
[0]
Set acknowledge mode
1 = Acknowledgment only using POWER ON.
[1]
Set acknowledge mode
2 = IMMEDIATE acknowledgment after removal of fault cause.
3 = Acknowledgment only for PULSE INHIBIT.
[19]
Set acknowledge mode
3
4
Changing the message type (fault <=> alarm) (for a maximum of 20 faults/alarms) <1>
p2118
[0]
0. Message number
[0]
[1]
1. Message number
[1]
[19]
19. Message number
[19]
5
6
fp_8075_70_eng.vsd
25.09.18 V01.05.00
Background
p2119
Set message type
1 = Fault (F)
Set message type
2 = Alarm (A)
3 = No message (N)
Set message type
7
8
Function diagram
- 8075 -
SINAMICS DCM/DCP