Signal sources for ZSW1_BM for telegram 220
Signal
Meaning
ZSW1.0
1 = Ready to switch on
ZSW1.1
1 = Ready
ZSW1.2
1 = Operation enabled
ZSW1.3
1 = Fault effective
ZSW1.4
0 = Coasting down active (OFF2)
ZSW1.5
0 = Quick stop active (OFF3)
ZSW1.6
1 = Switching on inhibited active
ZSW1.7
1 = Alarm effective
ZSW1.8
1 = Speed setpoint - actual value deviation within tolerance
ZSW1.9
1 = Control requested
ZSW1.10
1 = f or n comparison value reached or exceeded
ZSW1.11
1 = Torque limit not reached
ZSW1.12
1 = Open holding brake
ZSW1.13
Reserved
ZSW1.14
Reserved
ZSW1.15
Reserved
<1> ZSW1_BM is formed via binector-connector converter (BI: p2080[0...15], inversion: p2088[0].0...15).
<2> The drive object is ready for acceptance.
1
2
DO: DC_CTRL
PROFIdrive - ZSW1_BM status word sector metal interconnection
<2>
p2080[12] = r0899.12
<3>
<3>
<3>
3
4
<1>
Interconnection
Function diagram
Inverted
parameter
p2080[0] = r0899.0
[2585.7]
p2080[1] = r0899.1
[2585.7]
p2080[2] = r2811.0
[2655.8]
p2080[3] = r2139.3
[2548.7]
p2080[4] = r0899.4
[2585.7]
p2080[5] = r0899.5
[2585.7]
p2080[6] = r0899.6
[2585.7]
p2080[7] = r2139.7
[2548.7]
p2080[8] = r2197.7
[2534.7]
p2080[9] = r0899.9
[2585.7]
p2080[10] = r2199.1
[2537.7]
p2080[11] = r1407.7
[6830.7]
[2585.7]
<3>
<3>
<3>
<3> Interconnection is not inhibited.
5
6
fp_2428_13_eng.vsd
28.08.18 V01.05.00
PROFIdrive sampling time
7
Function diagram
SINAMICS DCM
8
- 2428 -