Arm Lk
0.0...1000.0 [mH]
p51592[D] (0.0)
V_supp rated val
Armature circuit
Red Ia rated [A]
Arm 1U1/1V1/1W1
r50072[1]
10...2000 [Vrms]
p50078[0] (400)
Explanations:
Ra:
Resistance of the armature circuit of the motor.
La:
Inductance of the armature circuit of the motor.
Rs:
Resistance of the interface transformer/smoothing reactor in 12-pulse mode.
Ls:
Inductance of the interface transformer/smoothing reactor in 12-pulse mode.
Lk:
Commutation inductance.
<1> Reduction factors p51591, p51595:
The percentage value to which the inductance drops at a current dictated by p50100 (motor rated armature current).
(For non-current-dependent inductances, this value is 100 %.)
1
2
DO: DC_CTRL
Armature circuit control - Armature circuit model parameters
V_sh-cct Uk p.u. [%]
r51598
f_line [Hz]
r50017[0]
[6950.5]
Ia act 6 mot cyc [%]
[6851.6]
r52107
3
4
R_intph 12-pulse
Rs
0.000...1000.000 [ ]
[6855.6]
p51596[D] (0.000)
Ia ctr Ra s_src
p51590[C]
(1)
0
Ra
Ra_eff
[6853.4]
0.000...1000.000 [ ]
[6855.5]
p50110[D] (0.000)
L_intph red fact
10...100 [%]
L_intph 12-pulse
p51595[D] (100)
0.00...1000000.00 [mH]
p51594[D] (0.00)
<1>
[6950.5]
Ls
[6855.6]
5
6
fp_6854_13_eng.vsd
28.09.18 V01.05.00
L_armat red fact
10...100 [%]
La
p51591[D] (100)
0.000...1000000.000 [mH]
p50111[D] (0.000)
<1>
f_line [Hz]
Armature circuit
r50017[0]
La_eff
7
Function diagram
SINAMICS DCM
1000 μs
[1721]
[6855.6]
8