Five parameters are used to manage the ventilation (one for each phase). The parameters define the fan operation as
either continuous or in parallel with the compressor/thawing heater. These parameters are: F29, F30, F31, F32, F33.
At the end of the thawing cycle the buzzer sounds, after which the machine moves on to a conservation phase, its
setpoint set by parameter r31 for an indefinite period.
Defrosting cycles cannot be carried out during thawing, whereas automatic defrosting (at intervals set by parameter)
is possible during the post-defrosting conservation phase.
If the door is opened, the machine will operate based on the value of parameter i0.
Cabinet sterilisation
4.9
Cabinet sterilisation is a cycle that is only available if the load managed by output K5 is the UV lamp (u2 = 1).
In order to carry out a sterilisation it is essential that there is no pre-cooling taking place and that the door is closed.
Access the SPECIAL CYCLES menu using the
appear and the next time
Sterilisation ends when the time set by parameter u6 has elapsed, after the
seconds or if the door is opened.
During sterilisation the cabinet sterilisation relay is active. If parameter u11 is set to 1, the evaporator fans are also
active.
key and select STERILISATION: at this point the start screen will
is pressed the cycle will start.
15
set 1 = initial setpoint
set 2 = final setpoint
key has been pressed for 2