Sammic AT-3 Manual De Instrucciones página 81

Ocultar thumbs Ver también para AT-3:

Publicidad

Idiomas disponibles

Idiomas disponibles

u2
2
0
u5
2
-50
u6
5
1
u7
40
-50
u8
2
0
u11
0
0
PAR.
DEFAULT
MIN.
Hr0
1
0
Loc
- - - -
- - - -
SEn
70
60
PAS
-19
-99
PA1
426
-99
PA2
824
-99
rE0
5
1
rE1
1
0
bLE
1
0
Load managed by output K5
0=cabinet light
1=UV lamp
3
- - - -
2= needle probe heater
3=alarm
Cabinet temperature over which the door heaters are switched
99
ºC
off
240
min
Time the UV lamp is on for the sterilisation cycle
Temperature to end needle probe heating;
199
ºC
see also parameter u8
Maximum duration of needle probe heating;
240
min
see also parameter u7
0 = needle probe heating is disabled
Enable evaporator ventilation during sterilisation (only valid if
u1=1)
1
- - - -
0=no
1=yes
MAX.
U.M.
SECURITY AND EVLINK DATA-LOGGING
Enable clock
1
- - - -
0 = no
1 = yes
- - - -
- - - -
Unused
120
- - - -
Key sensitivity setting
Password setting for parameter editing
999
- - - -
Regardless the value set, access to parameter editing is always
enabled by the superpassword 743
999
- - - -
EVconnect/EPoCA level 1 password
999
- - - -
EVconnect/EPoCA level 2 password
EVLINK data recording interval during blast chilling, blast
240
min
freezing, ice cream hardening and fish sanitation
Selection of values sampled by EVLINK
0 = none
1 = HACCP data (cabinet temperature, needle, cycle duration,
2
- - - -
type of cycle, total blast chilling time, HACCP alarms)
2 = SERVICE data (all temperatures, all events, all alarms, all
cycles)
Serial port connectivity configuration
0 = free
99
- - - -
1 = forced for EVconnect or EPoCA
2-99
=
28
EPoCA local network address
EN