5.6.4
Connection of transmitter to flowmeter sensor in Zone 1 / Div. 1
FCT330, FCT350 transmitter to FCB330, FCB350 flowmeter sensor
92 91
89
SE
Fig. 26
1 Equipotential bonding (PA)
Terminal
Corresponding wire color
85
White
86
Brown
87
Green
88
Yellow
89
Black
90
Violet
IMPORTANT (NOTE)
The wires must be connected in pairs in order to ensure EMC protection.
The following flowmeter sensor / transmitter combinations are permitted:
— FCB330 flowmeter sensor with FCT330 transmitter
— FCB350 flowmeter sensor with FCT350 transmitter
Change from one to two columns
90
93
94
95
96
87
88
85
Function
Sensor 1
Sensor 1
Sensor 2
Sensor 2
Temperature
Temperature
86
Terminal
Corresponding wire color
91
Gray
92
Pink
93
-
94
-
95
Blue
96
Red
CoriolisMaster FCB330, FCB350 | CI/FCB300-X1 Rev. C EN - 27
FCT330-A1/F1
FCT350-A1/F1
1
(Zone 1 / Div. 1)
FCB330-A1/F1
FCB350-A1/F1
(Zone 1 / Div. 1)
1
G10330-01
Function
Driver
Driver
Not used
Not used
Temperature
Temperature