5.5

Connecting the flowmeter sensor

5.5.1

Metal terminal box for ProcessMaster and HygienicMaster

Connections can only be made with the power supply switched off.
The device must be earthed according to instructions. The sensor is connected to the
transmitter via the signal / magnetic coil cable (part no. D173D027U01 or D173D031U01).
1S E1 E2 2S 3 D2 D1 M2 M1
Fig. 33
1 Earth wire.
2 Earth clamp.
4 Braided shield (D173D027U01 only).
Terminal
Description, wire color
M1
Magnetic coil, brown
M2
Magnetic coil, red
D1
Data line, orange
D2
Data line, yellow
PE
Shielding
3
Measurement potential, green
2S
Shield for E2
E2
Signal line, blue
E1
Signal line, violet
1S
Shield for E1
CI/FEX300/FEX500-X1
1S E1 E2 2S 3 D2 D1 M2 M1
1
2
4
D173D027U01
5 Foil shield D1, D2 (D173D031U01 only).
6 Continuity wire of the foil shield (D1, D2)
FEX300, FEX500
1S E1 E2 2S 3 D2 D1 M2 M1
D173D031U01
(D173D031U01 only).
Electrical connections
5
1
6
2
G00671-02
EN - 35