Descargar Imprimir esta página

Grundfos Control MPC Serie Manual De Instrucciones página 36

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 155
8.7.10 Proportional pressure (4.1.7)
Fig. 47 Proportional pressure
Description
The function can only be enabled in pressure-controlled systems
and it automatically adapts the setpoint to the actual flow rate to
compensate for flow-dependent dynamic losses. As many
systems are designed with extra flow capacity, the estimated
maximum flow rate (Qpmax) can be entered manually. In systems
with CR pumps, the pump curves can be used to calculate the
maximum flow rate at the selected setpoint. Set a filter factor to
prevent fluctuation.
If the multisensor function is enabled, it will have a
higher priority than the proportional pressure which
will be overruled.
The adaptation can be linear or square. See fig. 47.
H
C
B
A
Fig. 48 Proportional pressure
Pos.
Description
Pressure at zero flow. Starting point of proportional-
A
pressure control (influence at zero flow = x % of
setpoint)
B
Qpmax
C
Setpoint
The function has these purposes:
to compensate for pressure losses
to reduce the energy consumption
to increase the comfort for the user.
36
Setting range
Selection of control mode
Influence at 0 flow
Estimated flow rate
Filter factor.
Setting via the operating panel
Settings > Primary controller > Proportional pressure.
1. Select: Enabled.
2. Select:
Adaptation
Linear or Square.
3. Set: Influence at 0 flow.
4. Set: Filter factor.
5. Select: Use pump curve or Enter value.
6. Set "Qpmax" if you select "Enter value".
Factory setting
The function is disabled.
Q

Publicidad

loading

Este manual también es adecuado para:

Control mpc e 6x 000a dol u1 w a o