Cell Probe Alarm; Door Micro-Switch Alarm; Alarm - Differential Thermal Breaker - Oil Pressure; Automatic Reset Minimum Pressure Switch Alarm - Sammic ABS-15/2 Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

30 seconds) until the silencer button is pressed (minus (6)).
Display: The display shows the scrolling text "AL02 - SONDA
PRODOTTO 1(2) DIFETTOSA - FAULT PRODUCT PROBE
1(2). The symbol flashes RED (14)
Reset: Press the alarm silencer button (with beeper off) or
exclude with parameter "/9" (temperature chilling disabled)

16.3 Cell probe alarm

Cause: Being outside the operating range (-50°C / +100°C)
for more than 30 seconds.
Effect: If START is given to a positive chilling (both with
Time and Temperature) or if the latter is already in progress,
it immediately goes into pause-work positive storage mode
(C5 and C6 parameters).
If START is given to a negative chilling (both with Time
and Temperature) or if the latter is already in progress, it
continues (as it is not conditioned by the cell temperature
(until passing into negative storage which will be in pause-
work mode (C5 and C7 parameters). If the event takes over
during storage, this continues in pause-work mode.
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) until the silencer button is pressed.
Display: The display shows the scrolling text "AL03- SONDA
CELLA DIFETTOSA - FAULT ROOM PROBE"
Flashing RED symbol (14)
Reset: It resets by itself if the value of the probe is activated.
Note: With cell probe anomaly it is in any case possible
to perform RUN+HARD chilling (compressor goes into
continuous mode).

16.4) Door micro-switch alarm

Cause: Active input for more than 5 minutes (uF parameter)
with machine in start.
Effect: The blast chiller behaves as described in the sec-
tion "7 Door opening 7".
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) until the silencer button is pressed.
Display: The display shows the scrolling text "PORTA AP-
ERTA - OPEN DOOR"
The symbol (14) flashes YELLOW
Reset: Press the alarm silencer button (with beeper off),
or it resets by itself if the input status is activated
17
16.5 Alarm - Differential Thermal Breaker - Oil
Pressure
Cause: When the input alarm is activated for more than 5
seconds
Effect: It places the machine in STOP. Inhibition of all the
buttons except that of silence/reset, entering the parameter
menu and ON/OFF.
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) until the silencer button is pressed.
Display/LED: The display shows the scrolling text "AL06-
MAGNETOTERMICO-PRESS. OLIO - BREAKER - OIL
PRESS."
Flashing RED symbol (14)
Reset: pressing the off beeper alarm silencer button and
alarm cause disappearance.
16.6 Automatic reset minimum pressure
switch alarm 16.6.
Cause: When the machine is in start the alarm input is ac-
tivated for more than 5 seconds (with machine in STOP it
is not activated). The alarm is inhibited for approximately 2
minutes with each compressor start. The alarm is inhibited
during "pump downs".
Effect: It places the machine in STOP. Inhibition of the
Start/Stop and Defrost buttons
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) until the silencer button is pressed.
Display/LED: The display shows the scrolling text "AL07-
PRESSIONE MINIMA - MIN. PRESSURE".
Flashing RED symbol (14)
Reset: Pressing the off beeper alarm silencer button or
switching off and switching on the card again (stand-by).

16.7 Automatic reset Kriwan Alarm

Cause: When the input is activated with machine in start for
more than 5 seconds, at least 3 times in the same cycle.
Effect: Each time only the compressor stops and starts up
again when the input is activated. Upon the third time the
machine is placed in STOP.
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) until the silencer button is pressed.
Display/LED: If the Kriwan alarm is activated, for the first
two times only the word "Kriwan" appears, alternating with
the Temperature and Time values represented, without lock-
ing the machine but only the compressor. Upon the third
71503136-0-R000