Description of the autotest function
During the autotest the display shows
In case of failure for intervention of the membrane pressure switch, blinking
FAIL
on. After blinking
and led (B) on.
To reset, turn OFF the control panel, check and correct the anomaly. Switch on the control panel,
button and the current time appears.
The autotest is interrupted in case of intervention of the duty pump pressure switch.
The self-test is interrupted (message FAIL) under the following conditions:
-
The membrane pressure switch which is installed on the pump is intervened. The pressure is lower than the calibration
value of 1 bar.
-
Start failure of the pump.
Offset the starting time of the self-test procedure by at least 5 minutes for each electric pump.
The purpose of the self-test function is to provide for periodic start-ups designed to prevent any problems resulting from
protracted periods of pump inactivity. It is not intended as a substitute for the periodic checks required by standard EN12845,
section 20.
A qualified technician must wire the control panel correctly with reference to the wiring diagram
provided.
Enabling auto weekly test must be performed by qualified personnel.
8.8.2
Function with automatic shutdown for fire-hydrant networks
The main control panel contains a timer, on electronic card C128 (fig.6), that enables the automatic shutdown of the pump after
the system pressure has remained constantly above the starting pressure of the pump for the length of time specified by local
regulations (the default setting is 20 minutes).
To enable the automatic shutdown on the C128 card (fig.6)
JP8
C128
3 2 1
ON
LED TICK
Test procedure: you can check the auto off function without waiting for the set time. Automatically start the pump and press test
button on C128 (Figure 6). The pump must stop.
A qualified technician must wire the control panel correctly with reference to the wiring diagram
provided.
Enabling automatic shutdown must be performed by qualified personnel.
The automatic shutdown time must be according to local regulations, if present
Here you can note down the necessary data as shown on the rating plate. Specify this data when you call for service.
Engine type (engine rating plate)
Serial number of electric panel (plate on metal structure)
Engine serial number (engine rating plate)
Pump type (pump rating plate)
Installation date
tESt
, led (A) and (C) on (Figure 5). At the end led (C) on.
C128
TEST
1
2
3
4
GF006_A_SC
FAIL
, the test is not interrupted, led (A) and (B)
Jumper JP8 three positions (fig. 6):
23= Automatic shutdown doesn't enable (default), led tick OFF.
12= Automatic shutdown enable, led TICK red on and blinking.
Time of automatic shutdown is set by micro switches (Default 20
MIN).
1
2
3
10 MIN
ON
OFF
OFF
20 MIN
OFF
ON
OFF
30 MIN
OFF
OFF
ON
40 MIN
OFF
OFF
OFF
72
FAIL
fixed, press enter
4
OFF
OFF
OFF
ON