Monthly Check; Quarterly Check; Annual Check; Three-Yearly Check - Lowara GEM Instrucciones Para La Instalación Y El Uso

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

IN THE CASE OF FIRE-FIGHTING MODULES WITH DIESEL MOTORS
Restarting tests.
1) Restart the diesel pump immediately after it stops, by pressing the "START" manual starting test button.
2) Press the "STOP" button on the electric panel to stop the pump.
During the test:
- check the oil pressure (using the pressure gauges, when applicable, or another suitable measuring device).
- check the temperature of the motor and the coolant liquid.
- check the oil pipes.
- perform a general inspection to check for any leaks (of the fuel, coolant, exhaust fumes, etc.).
Check correct operation of all the heating and ventilation systems required to guarantee the correct environmental conditions for
the unit.
5.2.2

Monthly check

Each part of the monthly check must be performed at a frequency of no more than every four weeks.
These are (EN12845 para 20.2.3):
- Check the level and density of acid in all the cells of the starting batteries, using a densimeter. If the density of the acid is low,
check the battery charger and replace the batteries if necessary.
5.2.3

Quarterly check

Each part of the quarterly check must be performed at a frequency of no more than every thirteen weeks.
These are (EN12845 para 20.3.2):
Check for any changes to the system or risk category, etc.
 Check the sprinkler, pipes and pipe supports (refer to EN 12845, point 20.3.3.2 - UNI 10779).
 Start up the pumps and check their pressure and flow rate.
 Check operation of any generators – generating sets.
 Turn all the on-off valves to check their working order, and make sure they are all in their normal position.
 Check that the secondary supply of power provided by the Diesel generators is correct.
 Check the efficiency of the flow meters.
5.2.4
Biannual check
Each part of the biannual check must be performed at a frequency of no more than every six months.
These are (EN12845 para 20.3.3):
 Check the dry alarm valves and the other components of the system.
 Check the correct triggering of the alarms in the control room and/or in the fire department.
5.2.5

Annual check

Each part of the annual check must be performed at a frequency of no more than every twelve months.
These are (EN12845 para 20.3.4):
 Check the pressure and flow rate of the pumps with reference to the technical data plate.
 Check the Diesel pump "no start" alarm, in accordance with standard EN 12845 point 10.9.7.2 - UNI 10779 (perform six
starting attempts on the two batteries in alternation).
After the six attempts check activation, on the electric panel:
of the no start LED,
of the no start alarm contact.
Press the "START" manual test button immediately after the test to restart the motor.
 Check the working order of the float valves and filters in the tanks.
5.2.6

Three-yearly check

Each part of the three-yearly check must be performed at a frequency of no more than every three years.
These are (EN12845 para 20.3.5):
 Check for corrosion both INSIDE and outside the tanks and touch up the protective coating as necessary.
 Check the on-off and check valves and replace any that are damaged or faulty.
5.2.7
Ten yearly check
After no more than every ten years, clean all the water tanks and check the waterproofing on the inside (EN12845 para 20.3.6).