SC Series Controllers
Configuration
The SC controller has no default I/O mapped on the Ethernet/IP bus. The I/O must be assigned before an EDS
file can be obtained. "Faults" to assign and configure the Ethernet/IP I/O.
EDS Button
Under Setup Card header -> Select Ethernet/IP card -> Select EDS button
Connect a USB memory stick to the USB port on the bottom of the SC controller. Open the device net menu.
Click on the EDS button to export the EDS file to the memory stick.
EDS interactive menu button creates an EDS file equivalent to the Ethernet/IP I/O map created.
Use this controller generated EDS file in the PLC to which the SC controller is connected.
If the Ethernet/IP I/O map is changed, a new EDS file must be generated.
Save the changes.
8.1.4.3
Profinet
Under Setup Card header -> Select Profinet Card
This tab appears on the SC controllers only when the Profinet option is installed.
Profinet:
● Profinet I/O Device
This information is received when connecting the SC controller to Profinet control device using its optional
RJ-45 jack and cannot be modified.
● IP Address
The IP Address of the Alpha controller's Profinet port.
● Subnet Mask
The Subnet address of the Alpha controller's Profinet port.
● Gateway
The Gateway address to a connecting network.
● Name
This is the name of given to the controller for lookup by the controlling PLC to determine the IP Address of
the Profinet port on the Alpha controller. Valid device names are defined in the Profibus standard, but in
general must obey the following rules:
The device name can consist of one or more labels, each separated by a period (.).
Each label consists of numbers and lower-case letters, and may have embedded hyphens (-).
Each label can be up to 63 characters long, and the total device name can be up to 240 characters long.
The following examples are valid device names:
● rmc150e
● rmc150e-1
● rmc150e-1.company.com
● Physical
This is the MAC id of the RJ45 jack on the Alpha controller. This value comes from the Ethernet board in-
side and cannot be changed.
80 / 1032