Maintenance; Lubricants; Maintenance Intervals - Wilo EMU FA Serie Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 103

MAINTENANCE

8. Maintenance
ELECTROCUTION hazard!
There is a risk of fatal electric shocks when
performing work on electrical devices. With
all maintenance or repair work, the pump
must be disconnected from the mains and
secured against being switched on again
without permission. Damage to the power
supply cable may only be rectified by a quali-
fied electrician.
FATAL injury hazard due to impermissible
work!
Maintenance and repair work which may
impair explosion protection may only be per-
formed by the manufacturer or by authorized
service centers.
Also note the additional information in the
appendix!
• Before performing maintenance or repair work,
switch off and dismount the pump as described in
the "Decommissioning/disposal" section.
• After completing maintenance or repair work, the
pump must be installed and connected according
to the Installation section.
• The pump must be switched on as described in
the "Commissioning" section.
Note the following information:
• All maintenance and repair work must be carried
out by Wilo customer service, authorized service
centers or by trained specialist personnel with ut-
most care, in a safe workplace. Proper protective
clothing is to be worn.
• This manual must be available to the maintenance
personnel and its instructions must be followed.
Only the maintenance and repair work listed here
may be performed.
Further work and/or structural changes may
only be carried out by Wilo customer service.
• When carrying out work in basins and/or con-
tainers, the respective local protection measures
must be observed in all cases. A second person
must be present for safety reasons.
• Only lifting equipment that is in a technically
perfect condition and load-carrying equipment
that has been officially approved may be used for
lowering and raising the pump. When lifting and
lowering the pump, make sure that it does not
become jammed. If, however, the pump does be-
come jammed, the lifting forces must not exceed
1.2 x the pump weight! The maximum bearing
capacity should never be exceeded!
Make sure that all fastening devices, ropes and
safety devices of the lifting equipment are in
a technically perfect condition. Work may only
commence if the lifting equipment has been
checked and found to be in perfect working
order. If it is not inspected, fatal injuries may
result.
Installation and operating instructions Wilo-EMU FA+T-Motor
• Electrical work on the pump and system must be
carried out by an electrician. Defective fuses must
be replaced. Never attempt to repair them! Only
fuses at the specified current and of the pre-
scribed type may be used.
• When working with flammable solvents and
cleaning agents, fires, naked lights and smoking
are prohibited.
• Pumps that circulate fluids hazardous to health,
or that come into contact with these fluids, must
be decontaminated. It must be ensured that no
dangerous gases can form or are present.
• If injuries involving hazardous fluid or gases
occur, first-aid measures must be performed in
accordance with the notices in the workplace and
a doctor should be called immediately.
• Lubricants, such as oil and grease, must be col-
lected in suitable vessels and disposed of properly
(in accordance with the 75/439/EEC directive and
with Sections 5a, 5b of the German Waste Act
(AbfG)). Appropriate protective clothing must be
worn for maintenance and repair work. It must
be disposed of in accordance with waste code
TA 524 02 and EC Directive 91/689/EEC. Only
lubricants expressly recommended by the manu-
facturer may be used. Oils and lubricants should
not be mixed.
• Only use genuine parts made by the manufac-
turer.

8.1. Lubricants

8.1.1. Overview of white oils
The sealing chamber is filled with a white oil that
is potentially biodegradable.
We recommend the following oil types for an oil
change:
• Aral Autin PL
• Shell ONDINA G13, G15 or G17
• Esso MARCOL 52 or 82
• BP Energol WM2
• Texaco Pharmaceutical 30 or 40
All of these oil types are approved for use with
foods in accordance with USDA-H1.
Filling quantities
Always fill the sealing chamber up to the filling
opening with white oil. For the exact filling quan-
tity, please see the technical data specific to the
order.
8.1.2. Overview of greases
The following can be used as grease in accor-
dance with DIN 51818/NLGI class 3:
• Esso Unirex N3

8.2. Maintenance intervals

To ensure reliable operation, various maintenance
tasks must be carried out regularly.
The maintenance intervals must be determined
according to the demands on the pump. If strong
vibrations occur during operation, the pump or
installation must be checked, regardless of the
maintenance intervals.
English
61

Publicidad

Tabla de contenido
loading

Tabla de contenido