Quick Start Commissioning - Control Techniques UNIDRIVE SP1201 Guía Rápida

Ocultar thumbs Ver también para UNIDRIVE SP1201:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Safety
Product
Mechanical
Information
Information
Installation
7.2

Quick Start commissioning

7.2.1
Open loop
Action
Ensure:
Before
The drive enable signal is not given (terminal 31)
power-up
Run signal is not given
Motor is connected
Ensure:
Power-up
Drive displays 'inh'
the drive
If the drive trips, see Chapter 9 Diagnostics on page 39.
Enter:
Motor rated frequency in Pr 0.47 (Hz)
Enter
Motor rated current in Pr 0.46 (A)
motor
Motor rated speed in Pr 0.45 (rpm)
nameplate
details
Motor rated voltage in Pr 0.44 (V) - check if
connection
Set
Enter:
maximum
Maximum frequency in Pr 0.02 (Hz)
frequency
Enter:
Acceleration rate in Pr 0.03 (s/100Hz)
Set accel. /
Deceleration rate in Pr 0.04 (s/100Hz)
decel.
fitted, set Pr 0.15 = FAST. Also ensure Pr 10.30 and Pr 10.31
rates
are set correctly, otherwise premature 'It.br' trips may be
seen.)
32
Electrical
Getting
Menu 0
Installation
Started
www.controltechniques.com
Running
Advanced
Diagnostics Appendix
the motor
parameters
Detail
or
(If braking resistor
Unidrive SP Short Form Guide
UL Listing
Information
Mot X XXXXXXXXX
No XXXXXXXXXX kg
°
IP55
I.cl F
C 40 s S1
-1
V
Hz
min
kW
cosφ
A
230
50 1445 2.20 0.80 8.50
400
4.90
CN = 14.5Nm
240
50 1445 2.20 0.76 8.50
415
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
0.02
t
100Hz
t
0.03
0.04
Issue Number: 1